Spanish researchers develop passive cooling nanomaterial with building potential
Spain – Researchers in Spain have developed a nanostructured material capable of cooling sun-exposed surfaces without electricity, with potential applications on building roofs and façades that could reduce demand for active cooling.
Outdoor testing in Madrid recorded a maximum temperature reduction of 12.9°C compared with an empty reference box under peak solar irradiance of 962 W/m². However, the material has not yet been tested on a building or demonstrated a reduction in air-conditioning energy consumption.
Passive cooling under direct sunlight
The material was developed by researchers in the Functional Nanoscale Devices for Energy (FINDER) group at the Institute of Micro and Nanotechnology (IMN-CNM), part of Spain’s National Research Council, CSIC.
The research uses passive daytime radiative cooling, which allows heat to be dissipated through infrared radiation without an external energy supply.
The team created three-dimensional nanostructures from polyvinylidene fluoride (PVDF), using nanoporous anodised aluminium oxide as a template. The resulting material is designed to reflect incoming solar radiation while emitting thermal radiation through the atmospheric transparency window between 8 and 13 micrometres.
Different cooling processes were used during manufacture, followed by ultraviolet treatment to increase the material’s solar reflectance.
12.9°C reduction recorded in outdoor tests
Tests were carried out outdoors on the roof of the IMN-CNM facility in Tres Cantos, Madrid, during summer conditions.
The best-performing free-standing 3D-PVDF sample achieved average solar reflectance of 82.4% and infrared emissivity of 96.7% across the 8–13 micrometre atmospheric window.
Researchers calculated a theoretical daytime cooling-power density of 182.3 W/m² under solar irradiance of 1,000 W/m².
Outdoor measurements recorded a maximum temperature reduction of 12.9°C relative to an empty reference box when peak solar irradiance reached 962 W/m². The figure should therefore not be interpreted as the material operating 12.9°C below ambient air temperature.
Potential to reduce active cooling demand
The researchers say the manufacturing approach could potentially be adapted to industrial processes, with applications including building roofs and façades, electronic devices, vehicles and other thermal-management systems.
For buildings, the potential lies in reducing solar heat gains at the external surface and consequently lowering the amount of active cooling required.
However, the technology remains at the materials-development stage. No building-scale installation, commercial product or measured reduction in HVAC electricity consumption has been reported.
Further development and larger-scale testing will therefore be needed to establish how the material performs when incorporated into real building envelopes and what effect it could have on cooling loads.